A typical vibration dispute starts like this. A contractor drives piles or runs a vibratory roller, a neighbour finds a crack, and both sides produce a number. The contractor quotes 15 mm/s, the neighbour's engineer quotes 5 mm/s, and both are citing a real standard. They are simply measuring different things at different places on the building.

This is the comparison for Thailand, Malaysia, Vietnam and Indonesia, the four countries in the region with their own written criteria, and how each relates to the two European standards that sit behind almost all of them: DIN 4150-3 (Germany) and BS 7385-2 (UK).

A vibration limit means nothing without three things: the frequency at the peak, the measurement position, and whether the vibration is short-term or continuous.

The comparison

CountryInstrument (current)StatusResidential building (damage)Measured whereBasis
ThailandNational Environment Board Notification No. 37 (B.E. 2553 / 2010)Legally binding5 mm/s below 10 Hz, rising to 15 mm/s at 50 Hz and 20 mm/s above 100 Hz; 15 mm/s horizontal at the top floor (5 mm/s if the vibration can cause fatigue or resonance)Foundation or lowest floor, within 0.5 m of ground; top floor; mid-span of each floor slabDIN 4150-3 values written as formulas; instrument to DIN 45669-1
MalaysiaDOE Guidelines for Environmental Vibration Limits and Control (2021)Guideline, applied through EIA and approval conditionsTransient: 15 mm/s at 4 Hz rising to 20 mm/s at 15 Hz and 50 mm/s at 40 Hz. Continuous: half of that (7.5 to 25 mm/s). DIN 4150-3 values also givenBase of the buildingBS 7385-2 (Fifth and Sixth Schedules) and DIN 4150-3; human response to BS 6472 and ISO 2631
VietnamQCVN 27:2025/BNNMT (in force 14 Nov 2025, replaces QCVN 27:2010)Legally bindingNo damage criterion. Construction annoyance limit 70 dB day, 65 dB night (Zones B to D); 65/60 dB in Zone AAt the affected receptor, minimum 15 min measurementWeighted vibration acceleration level, dB re 10⁻⁵ m/s², TCVN 6963
IndonesiaKepMenLH No. 49/1996 (Baku Tingkat Getaran)Legally bindingCategory 2 (buildings with existing cracks): 5 mm/s; Category 3 (good condition): 10 mm/s; Category 4 (strong concrete or steel): 10 to 40 mm/s; heritage 2 mm/sOn the buildingOwn categories by building condition; separate comfort criteria
Building damage criteria for a typical residential building, peak particle velocity (PPV) unless stated. Vietnam's criterion is an annoyance limit, not a damage limit.

Thailand is DIN 4150-3 in disguise

Notification No. 37 looks like a Thai standard because it writes the limits as formulas: for a Type 2 building (houses, shophouses, condominiums, hospitals, schools) the foundation limit between 10 and 50 Hz is 0.25f + 2.5 mm/s. Work it out and you get exactly the DIN 4150-3 line for dwellings: 5 mm/s at 10 Hz, 15 mm/s at 50 Hz, 20 mm/s at 100 Hz. Type 1 (factories, offices, warehouses) and Type 3 (monuments and fragile cultural buildings) follow the other two DIN lines in the same way.

Two details catch people out. First, the notification has two cases: vibration that cannot cause fatigue or resonance, and vibration that can. For a residential building the top-floor limit drops from 15 mm/s to 5 mm/s in the second case, which is where long piling campaigns and vibratory compaction often belong. Second, it specifies where the sensor goes: on the lowest floor near the outer wall, no higher than 0.5 m, fixed to the structure. A geophone sitting loose on a garden path is not a measurement under this notification, and a monitoring programme set up that way can be rejected as evidence.

Malaysia allows more, and says so

The 2021 DOE guideline replaced the 2007 edition and is far more complete: 118 pages covering human response, sensitive equipment, blasting and building damage. For damage it reproduces BS 7385-2, which permits 15 mm/s at 4 Hz for a residential building, rising to 50 mm/s from 40 Hz. That is three times the Thai figure at the same frequency. The guideline halves those values for continuous vibration, gives the DIN 4150-3 lines as an alternative, and is explicit that a limit does not guarantee the absence of cosmetic damage.

In practice the choice between BS 7385-2 and DIN 4150-3 is made in the EIA or the approval conditions. If you are the contractor, check which one before you price the monitoring. If you are the neighbour, check whether the reported figure is a transient or a continuous limit.

Vietnam regulates annoyance, not damage

QCVN 27:2025 replaced the 2010 regulation in November 2025. It is a human-response standard: a weighted acceleration level in decibels, 70 dB by day and 65 dB at night at most receptors near a construction site, with +10 dB allowed if the work lasts no more than two hours a day. It contains no building damage criterion. A Vietnamese project that monitors only to QCVN 27 has no answer when a wall cracks, so specify DIN 4150-3 or BS 7385-2 alongside it in the contract.

Indonesia grades by building condition

The 1996 decree is the only one of the four that classifies buildings by their state rather than their use: 5 mm/s for a building that already has visible cracks, 10 mm/s for one in good condition. That makes a pre-construction condition survey part of the limit itself. Without photographs and a crack log before work starts, nobody can say which category a building was in.

What to put in a monitoring plan

  • State the criterion, the edition and the line or category for each receptor, for example DIN 4150-3:2016 Table 1 line 2 at the foundation, not just "DIN 4150".
  • Record the dominant frequency with every peak. Without it a Thai, German or British limit cannot be applied, and a 6 mm/s event at 8 Hz and at 45 Hz have very different meanings.
  • Set an alert level below the limit (70 to 80 percent of the limit is common practice) with real-time notification, so the contractor can change method before an exceedance rather than after it.
  • Do a condition survey of every receptor within the zone of influence before work starts. In Indonesia it decides the category; everywhere else it decides the argument.
  • Use a monitor whose calibration certificate is current and traceable. Thailand names DIN 45669-1 for the instrument; a court will ask for the certificate.

Geonoise runs construction vibration monitoring with online alerting to these criteria, and Acoustic Laboratory Thailand calibrates vibration sensors traceably. If you have a piling or demolition job next to occupied buildings, send me the site plan and the nearest receptors and I will tell you which limit governs and where the sensors should go.

Questions we are asked

What is the construction vibration limit for houses in Thailand?

Under National Environment Board Notification No. 37 (B.E. 2553), the limit at the foundation of a Type 2 building (houses, shophouses, condominiums, hospitals, schools) is 5 mm/s PPV below 10 Hz, 0.25f + 2.5 mm/s between 10 and 50 Hz, 0.1f + 10 mm/s between 50 and 100 Hz, and 20 mm/s above 100 Hz. At the top floor the horizontal limit is 15 mm/s, or 5 mm/s where the vibration can cause fatigue or resonance. These values are the same as DIN 4150-3.

Is Thailand's vibration standard the same as DIN 4150-3?

Yes in substance. NEB Notification No. 37 expresses the DIN 4150-3 guideline lines as frequency formulas for three building types, and requires an instrument to DIN 45669-1. Thailand adds a mandatory measurement position and a floor-slab limit of 20 mm/s vertical.

Which vibration standard does Malaysia use for building damage?

The DOE Guidelines for Environmental Vibration Limits and Control (2021) give BS 7385-2 guide values (transient: 15 mm/s at 4 Hz rising to 50 mm/s at 40 Hz for residential buildings; half of that for continuous vibration) and DIN 4150-3 values. The applicable one is usually fixed in the EIA or approval conditions.

Does Vietnam have a building damage vibration limit?

No. QCVN 27:2025/BNNMT, in force from 14 November 2025, sets human-annoyance limits as a weighted vibration acceleration level in dB (70 dB day and 65 dB night near construction in most zones). Building damage is not covered, so projects should specify DIN 4150-3 or BS 7385-2 separately.

Why do two engineers report different vibration limits for the same building?

Usually because they apply different standards (DIN 4150-3 is stricter than BS 7385-2 at low frequency), different positions (foundation versus top floor), or different cases (short-term versus continuous). Ask for the standard edition, the line or category, the measurement position and the dominant frequency at the peak.

Sources

  1. Thailand: NEB Notification No. 37 (B.E. 2553) on vibration standards to prevent impacts on buildings (full text)
  2. Malaysia: DOE Guidelines for Environmental Vibration Limits and Control (2021)
  3. Vietnam: QCVN 27:2025/BNNMT on vibration, issued by Circular 01/2025/TT-BNNMT
  4. Indonesia: KepMenLH No. 49/1996 on vibration levels (summary)
  5. Thailand: building vibration services and standards, Geonoise Thailand

More from Insights

Measurement Strategy 6 min read

Accredited or Traceable Calibration: Which One Your Tender or Audit Actually Asks For

Two certificates can look the same and carry very different weight. What ISO/IEC 17025 accreditation adds over traceable calibration, what ISO 9001 and ILAC actually require, and how to read a tender clause before you send an instrument away.

Read article
Noise Regulation 7 min read

Environmental Noise Limits Across ASEAN: Six Countries in One Table

Thailand, Malaysia, Singapore, Indonesia, Vietnam and the Philippines each set environmental noise limits in a different way. The residential figures, the metric behind them and the instrument they come from, checked against the regulations in October 2026.

Read article
Acoustic Strategy 5 min read

Why Noise Problems Often Remain Unsolved

Many noise problems are not caused by a lack of data. They remain unresolved because the wrong questions are asked at the beginning of a project.

Read article
Independent Consulting 4 min read

Why Independent Acoustic Assessment Still Matters

Today, many acoustic products and systems are marketed with impressive performance claims. Real-world acoustic performance, however, often depends heavily on installation quality, operating conditions, and measurement methodology.

Read article
Measurement Strategy 5 min read

Acoustic Measurement Is Only Valuable When It Supports Decisions

Modern acoustic instruments can generate enormous amounts of data. However, more data does not automatically create better decisions.

Read article